Tools / Occupant Load Calculator
Occupant Load Calculator Calculate occupant load, required number of exits, and minimum egress width using NFPA 101 (2021) Table 7.3.1.2 and Sections 7.3.3 / 7.4.1. Add one or more rooms, pick the use, enter the area.
Health-care occupancy (affects egress factors) Sprinklered (quick-response per 9.7)
Rooms / Areas + Add area Use
Assembly β concentrated use, no fixed seats β 7 sq ft Assembly β less concentrated, no fixed seats β 15 sq ft Standing space β 5 sq ft Bench-type seating β per 18 in. of length Waiting space β 3 sq ft Library β reading rooms β 50 sq ft Library β stack area β 100 sq ft Kitchens (commercial) β 100 sq ft Exercise rooms with equipment β 50 sq ft Exercise rooms without equipment β 15 sq ft Swimming pool deck β 30 sq ft Swimming pool (water surface) β 50 sq ft Museum exhibit β 30 sq ft Business use (general office) β 150 sq ft Airport traffic control tower observation level β 40 sq ft Classroom β 20 sq ft Shops & vocational rooms β 50 sq ft Day-care β 35 sq ft Inpatient treatment departments β 240 sq ft Sleeping departments β 120 sq ft Ambulatory health care β 100 sq ft Hotels & dormitories β 200 sq ft Apartment buildings β 200 sq ft Board & care (small) β 200 sq ft Detention & correctional β 120 sq ft Mercantile β street floor or below β 30 sq ft Mercantile β floors above street β 60 sq ft Mercantile β storage, receiving, shipping β 300 sq ft Mall building β covered mall β per IBC/NFPA 101 Annex Industrial β general & high hazard β 100 sq ft Industrial β special purpose β 200 sq ft Aircraft hangars (no repair) β 500 sq ft Storage (warehouse) β 500 sq ft Parking garage β 200 sq ft Mechanical equipment room β 300 sq ft
Total occupant load
0
persons
Required exits (min)
0
exits
Min stair width
0
inches Β· 0.3"/person
Min level/ramp width
0
inches Β· 0.2"/person
Code basis NFPA 101 Table 7.3.1.2 β Occupant Load FactorsNFPA 101 7.3.3.1 β Egress capacity: 0.3 in/person (stair), 0.2 in/person (level/ramp) for new, sprinklered, non-health-care. Health-care unsprinklered: 0.6 / 0.5.NFPA 101 7.3.4.1 & 7.4.1.2 β Minimum 2 exits for OL β€ 500, 3 for 501β1000, 4 for > 1000.IBC Table 1004.5 β Equivalent IBC occupant load factors (typically align with NFPA 101).Minimum corridor width in new business / health care and minimum stair width also apply β this tool calculates capacity-based minimum only. Use the larger of capacity width or prescribed minimum width (36", 44", 48", 72", etc.). Reminder: Occupant load is per story. For multi-story buildings, calculate each story separately, then size exits for the most populous story. Horizontal exits, fixed seating, and concentrated-use rooms have special rules β consult NFPA 101 Chapter 7 and your AHJ.